meta data
| export date |
2012-05-11 19:26:48 |
| generation date |
2012-05-11 22:51:36 |
| type name |
EF12 |
| type id |
372 |
| PublPrgr |
Power Entry Modules with Filter [shortcut:PG06] |
| PRV |
EF12.0034.2110.01 [id:12110] EF12.0035.1110.01 [id:12111] EF12.0035.1210.01 [id:12112] EF12.0572.1110.01 [id:12113] EF12.0699.2110.01 [id:12114] EF12.0699.2210.01 [id:12115] EF12.0885.2110.01 [id:12116] EF12.1034.3110.01 [id:12117] EF12.1089.1110.01 [id:12118] EF12.1164.1110.01 [id:12119] EF12.2105.2110.01 [id:12120] EF12.2196.1110.01 [id:12121] EF12.2196.1210.01 [id:12122] EF12.2561.1110.01 [id:12123] EF12.2961.1110.01 [id:12124] EF12.3103.2110.01 [id:12125] EF12.3103.2210.01 [id:12126] EF12.3104.1110.01 [id:12127] EF12.3104.1210.01 [id:12128] EF12.3107.3110.01 [id:12129] EF12.3107.3210.01 [id:12130] EF12.3197.1110.01 [id:12131] EF12.3297.2110.01 [id:12132]
|
General Informations
EF12 EMV Power Entry Modules with Filter: IEC Appliance Inlet C20 with Filter, Circuit Breaker TA45 (recessed)
Standard- or Medical-Filter
Description
| - |
Panel Mount: Screw-on mounting from front side |
| - |
3 Functions: Appliance Inlet Protection class I, circuit breaker type TA45 2-pole, Line filter in standard and medical version |
| - |
Quick connect terminals 6.3 x 0.8 mm |
Approvals
| - |
VDE Certificate Number:40001520 |
| - |
UL File Number:E72928 |
Characteristics
| - |
All single elements are already wired |
| - |
Line switch non-illuminated Illuminated version on request Thermal overload protection Optional with undervoltage- or remote trip release |
| - |
With EMC-shield |
| - |
Qualified for use in equipment according IEC/EN 60950 |
Other versions on request
| - |
Variant with notch for V-Lock mating Cordsets |
ReferencesAlternative: version without line filter
EF11
Weblinks
pdf,
General Product Information , Approvals,
RoHS ,
CHINA-RoHS ,
Mating Connectors , e-Shop, SCHURTER-Stock-Check, Distributor-Stock-Check,
Accessories ,
Product News
, PCS
Newly available variants corresponding to V-Lock mating cordset. The connector is equipped with a notch intended for use with the latching cordset. The cord latching system prevents against accidental removal of the cordset.
| Ratings IEC |
12 - 16 A @ Ta 40 °C / 250 VAC; 50 Hz |
| Ratings UL/CSA |
12 - 20 A @ Ta 40 °C / 125 VAC; 60 Hz |
| Leakage Current |
standard < 0.5 mA (250 V / 60 Hz) medical < 5 µA (250 V / 60 Hz) |
| Dielectric Strength |
> 1.7 kVDC between L-N > 2.7 kVDC between L/N-PE Test voltage (2 sec) |
| Allowable Operation Temp. |
-10 °C to 55 °C |
| Climatic Category |
10/055/21 acc. to IEC 60068-1 |
Degree of Protection
[?]
Term: IP-Protection
Explanation:
The IP code consists of a two-digit number, which indicates the respective degree of protection.
The first digit specifies the protection from the penetration of foreign objects, the second digit the protection from water penetration with harmful effects.
I. index number: protection from the penetration of foreign objects 0 non-protected
1 ≥ 50 mm diameter (back of hand)
2 ≥ 12.5 mm diameter (finger)
3 ≥ 2.5 mm diameter (tool)
4 ≥ 1 mm diameter (wire)
5 dust-protected
6 dust-tight
II. index number: protection from water penetration with harmful effects
0 non-protected
1 vertically dripping
2 dripping (15° tilted)
3 spraying
4 splashing
5 jetting
6 powerful jetting
7 temporary immersion (1 m, 30 min)
8 continous immersion 9K: water at high pressure / steam jet cleaning (Water that is addressed against the housing from any direction under increased pressure, should have no harmful effects.
|
from front side IP 40 acc. to IEC 60529 |
| Protection Class |
Suitable for appliances with protection class 1 acc. to IEC 61140 |
| Terminal |
Quick connect terminals 6.3 x 0.8 mm |
| Panel Thickness s |
Screw: max 8 mm Mounting screw torque max 0.5 Nm |
| Material: Housing |
Thermoplastic, black, UL 94V-0 |
| Appliance-Inlet/-Outlet |
C20 acc. to IEC/EN 60320-1, UL 498, CSA C22.2 no. 42 (for cold conditions) pin-temperature 70 °C, 16 A, Protection Class 1 |
| Circuit Breakers |
Acc. IEC/EN 60934, UL 1077, CSA 22.2 no. 235 2-pole rocker switch, illuminated or non-illuminated. Optional with undervoltage- or remote trip release Short circuit capacity Icn: at In < 3A/240VAC : 10 x In at In ≥ 3A/240VAC : 300A |
| Line Switch |
Rocker switch 2-pole, non-illuminated or illuminated, acc. to IEC 61058-1
Technical details
|
| Line Filter |
Standard and Medical Version, IEC 60939, IEC 60601 1, UL 1283, UL 544, EN 133 200, CSA C22.2 no. 8
Technical details
|
| MTBF |
> 100'000 h acc. to MIL-HB-217 F |
|
* --- Version TA45 with undervoltage release
|
|
Category / Description |
|
▲
| IEC Connector C19, Rewireable, Straight |
0104
|
| IEC Connector C19, Rewireable, Angled |
1651
|
| IEC Connector C19, Rewireable, Straight |
1652
|
| IEC Connector C19, Rewireable, Angled |
4790
|
| IEC Connector C19, Rewireable, Straight |
4795
|
|
|
|
|
▲
| Power Cord with IEC Connector C19, Straight |
1654
|
|
|
|
|
▲
| Divers Power Supply and Interconnection Cords 16 A |
CordSets15A
|
|
|
|
|
Description |
|
|
|
|
|
|
|
|
|